Description
All-in-one solar power solution
The EasySolar combines two MPPT solar charge controller and an inverter/charger in one enclosure. The product is easy to install, with a minimum of wiring.
Two solar charge controllers: 2x Blue Solar MPPT 100/50, 0r 2x Blue Solar MPPT 150/35
Up to six strings of PV panels can be connected to six sets of MC4 (PV-ST01) PV connectors.
The inverter/charger: MultiPlus Compact 24/3000/70-50 or 48/3000/35-50
The MPPT charge controllers and the MultiPlus inverter/charger share the DC battery connection. The batteries can be charged with solar power (2x BlueSolar MPPT) and/or with AC power (inverter/charger) from the utility grid or a Genset.
PowerAssist
Unique PowerAssist technology protects the utility or generator supply from being overloaded by adding extra inverter power when needed.
Unique solar application software
Several software programs (Assistants) are available to configure the system for various grid-interactive or stand-alone applications.
EasySolar | EasySolar 24/3000/70-50 | EasySolar 48/3000/35-50 |
Inverter/charger | ||
---|---|---|
Transfer switch | 50 A | |
INVERTER | ||
Input voltage range | 19 – 33 V | 38 – 63 V |
Output | Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0,1% (1) |
|
Cont. output power at 25 °C (3) | 3000 VA / 2500 W | |
Cont. output power at 40 °C | 2200 W | |
Peak power | 6000 W | |
Maximum efficiency | 94% | 95% |
Zero-load power | 15 W | 16 W |
Zero load power in search mode | 5 W | 5 W |
CHARGER | ||
AC Input | Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz Power factor: 1 |
|
Charge voltage ‘absorption’ | 28,8 V | 57,6 V |
Charge voltage ‘float’ | 27,6 V | 55,2 V |
Storage mode | 26,4 V | 52,8 V |
Charge current house battery (4) | 70 A | 35 A |
Charge current starter battery (A) | 4 | |
Battery temperature sensor | yes | |
Programmable relay (5) | yes | |
Protection (2) | a – g | |
Solar Charge Controller | ||
Model | 2x MPPT 100/50 | 2x MPTT 150/35 |
Maximum output current | 2x 50 A | 2x 35 A |
Maximum PV power, 6a,b) | 2x 1400 W | 2x 2000 W |
Maximum PV open circuit voltage | 100 V | 150 V |
Maximum efficiency | 98 % | |
Self-consumption | 10 mA | |
Charge voltage ‘absorption’, default setting | 28,8 V | 57,6 V |
Charge voltage ‘float’, default setting | 27,6 V | 55,2 V |
Charge algorithm | multi-stage adaptive | |
Temperature compensation | -16 mV / °C | -32 mV / °C |
Protection | a – g | |
COMMON CHARACTERISTICS | ||
Operating temp. range | -20 to +50°C (fan assisted cooling) | |
Humidity (non condensing): | max 95% | |
ENCLOSURE | ||
Material & Colour | aluminium (blue RAL 5012) | |
Protection category | IP 21 | |
Battery-connection | Four M8 bolts (2 plus and 2 minus connections | |
230 V AC-connectio | Screw terminals 13 mm2 (6 AWG) | |
PV connection | Six sets of MC4 (PV-ST01) PV connectors. | |
Weight | 21 kg | |
Dimensions (hxwxd) | 362 x 374 x 218 mm | |
STANDARDS | ||
Safety | EN 60335-1, EN 60335-2-29, EN 62109, IEC 62109 | |
Emission / Immunity | EN55014-1, EN 55014-2, EN 61000-3-3 | |
1) Can be adjusted to 60Hz and to 240V 2) Protection a. Output short circuit b. Overload c. Battery voltage too high d. Battery voltage too low e. Temperature too high f. 230VAC on inverter output g. Input voltage ripple too high |
3) Non linear load, crest factor 3:1 4) At 25 °C ambient 5) Programmable relay which can a. o. be set for general alarm, DC undervoltage or genset start signal function 6a) If more PV power is connected, the solar charge controllers will limit input power to 1400W resp. 2000W 6b) PV voltage must exceed Vbat + 5V for the controller to start. Thereafter minimum PV voltage is Vbat + 1V |