Nominal Voltage | 48VDC | |
Voltage Range | 44VDC – 54VDC | |
Maximum Charge Rate (0% -100% SOC) | 100A | |
Maximum Discharge Rate (100% – 0% SOC) | 100A | |
Maximum Charging Voltage | 54VDC | |
Internal Resistance | ≤3mΩ | |
DC to DC Roundtrip efficiency (@100A) | 99.10% | |
Operating Temperature | -30⁰C to 85⁰C | |
Galvanic Isolation | 1500V | |
Projected Cycle Life3
|
Supercap cell | 45 years |
Module Control Electronics | 10 – 15 years | |
Shelf Life2 | 10 years | |
Warehousing | Can be stored at any SOC without affecting cycle life | |
Remote Control Input | Battery Self-Check | |
Terminal Type | F12 | |
Module Casing Material | Aluminium | |
Dimensions (w x d x h) | 600mm x 534mm x 200mm | |
Weight | Approx.75kg | |
Self-discharge4 | 5% after 25 days | |
Alarm | Audible alarm in the event of Over-Charge, Over-Discharge, Over-Temperature, Over-Current | |
Data Available | Energy (kWh) delivered to date on the LCD Display | |
CE Certification5 | EN55022:2010/AC:2011,EN61000-3-2:2006+A2:2009, EN61000-3-3:2008, EN55024:2010 | |
Precautions | ||
---|---|---|
Alarm | In case of alarm, immediately rectify / attend to the cause of the alarm | |
Physical Damage | In case the module is physically damaged due to any event, do not install and energize the module under any circumstances and contact an authorized technician | |
Short Circuit | Ensure precautions to prevent short-circuit under all circumstances | |
Galvanic isolation | When connecting to external devices ensure that galvanic isolation does not exceed 1500V | |
Charge / Discharge Current | Under no circumstances must the charge / discharge current exceed 100A | |
Charging Voltage | Under no circumstances must the charging voltage exceed 54VDC for more than 60 seconds. | |
Charge Cycle | During charge cycle ensure never to exceed constant voltage of 54VDC and constant current of 100A | |
Series Connection | To connect modules in series, ensure all modules are at 100% SOC before connecting. Do not connect otherwise | |
Maximum number of modules that can be connected in series | 18 |