Sirius Supercapacitor – Sirius Energy Storage Module

Categories: ,

Description

Nominal Voltage 48VDC
Voltage Range 44VDC – 54VDC
Maximum Charge Rate (0% -100% SOC) 100A
Maximum Discharge Rate (100% – 0% SOC) 100A
Maximum Charging Voltage 54VDC
Internal Resistance ≤3mΩ
DC to DC Roundtrip efficiency (@100A) 99.10%
Operating Temperature -30⁰C to 85⁰C
Galvanic Isolation 1500V
Projected Cycle Life3
Supercap cell 45 years
Module Control Electronics 10 – 15 years
Shelf Life2 10 years
Warehousing Can be stored at any SOC without affecting cycle life
Remote Control Input Battery Self-Check
Terminal Type F12
Module Casing Material Aluminium
Dimensions (w x d x h) 600mm x 534mm x 200mm
Weight Approx.75kg
Self-discharge4 5% after 25 days
Alarm Audible alarm in the event of Over-Charge, Over-Discharge, Over-Temperature, Over-Current
Data Available Energy (kWh) delivered to date on the LCD Display
CE Certification5 EN55022:2010/AC:2011,EN61000-3-2:2006+A2:2009, EN61000-3-3:2008, EN55024:2010
Precautions
Alarm In case of alarm, immediately rectify / attend to the cause of the alarm
Physical Damage In case the module is physically damaged due to any event, do not install and energize the module under any circumstances and contact an authorized technician
Short Circuit Ensure precautions to prevent short-circuit under all circumstances
Galvanic isolation When connecting to external devices ensure that galvanic isolation does not exceed 1500V
Charge / Discharge Current Under no circumstances must the charge / discharge current exceed 100A
Charging Voltage Under no circumstances must the charging voltage exceed 54VDC for more than 60 seconds.
Charge Cycle During charge cycle ensure never to exceed constant voltage of 54VDC and constant current of 100A
Series Connection To connect modules in series, ensure all modules are at 100% SOC before connecting. Do not connect otherwise
Maximum number of modules that can be connected in series 18